1MRS 751108-MUM
3URWHFWLRQ5HOD\
Technical Reference Manual, General
5(;
55
$SSHQGL[$,(&EXV
)XQFWLRQVVXSSRUWHGE\5(;
*HQHUDOSULQFLSOHRIDSSOLFDWLRQGDWDPDSSLQJ
The interface between the REX 521 physical applications and the IEC 60870-5-103
application layer is done accordingly:
$OWHUQDWLYH$
If a corresponding REX 521 application signal is defined by the IEC 60870-5-103
standard, the alternative A is used.
$OWHUQDWLYH%
Refer to Digitale Stationslettechnik - Ergänzende Empfelungen zur Anwendung in
Verteilnetzstationen by Vereinigung Deutscher Elektrizitätswerke.
$OWHUQDWLYH3
Private definitions are basically used because of two reasons:
1. The standard does not define the signal.
2. The signal is defined by the standard but the REX 521 application signal
interface differs from this model.
&ODVVGDWDEXIIHULQJDQGSULRULWLHV
The internal IEC 60870-5-103/Class 1 buffer inside the REX 521 unit can store up
to 50 spontaneous events. The interrogation events and the possible response
messages, that also are part of the class 1 data, do not occupy space in the buffer.
The priority of the different categories of the pending class 1 data is always so that
the response messages have the highest priority, thereafter the spontaneous events
and finally the interrogation events. The IEC_103 data cannot be filtered by using
event masks.
)XQFWLRQ
)XQFWLRQ
FRGH
&RPPHQW
Reset CU 0 Replies with the identification string
User data 3 • GI command
• time synchronization (unicast)
• application control commands
Broadcast 4 Time synchronization only
Reset FCB 7 Replies with identification string
Request Access Demand 8
Request Status of Link 9
Request Class 1 Data 10
Request Class 2 Data 11