4.6.5 Control menu
By pressing on the Control menu, the next
control menu tree is displayed.
Start Battery Test: this is the command that
allows the UPS to do a battery test.
Reset Fault status: when a fault occurs, the UPS
will stay in Fault mode and the alarm will continue
to ring. Enter this menu to reset error status: then
the UPS stops the alarm and recovers to bypass
mode. The cause of the fault should be checked
and corrected before the UPS is reset manually.
Restore factory settings: all the settings are reset
to default factory settings. Can only be done in
bypass mode.
—
26 Control menu
—
27 Identification menu
4.6.6 Identification menu
By pressing on the Identification menu, the
next identification menu tree is displayed.
Identification information includes UPS serial
number, firmware serial number and model type.
Press ESC for more than 3 s to return to the last
main menu tree.
—