38
ABB UPS PRODUCTS AND SOLUTIONS
BATTERY
AUTONOMY
11T G2 6kVA B 11T G2 6kVA B2 11T G2 6kVA S 11T G2 10kVA B 11T G2 10kVA B2 11T G2 10kVA S
UPS internal
batteries
4 / 6 / 10 / 27 5 / 8 / 14 / 37 N/A 2 / 4 / 7 / 17 3 / 5 / 9 / 23 N/A
UPS + 1 EBM
18 / 27 / 47 /123 24 / 37 / 64 / 171 18 / 27 / 49 / 133 12 / 18 / 31 / 83 16 / 24 / 43 / 114 8 / 13 / 23 / 64
UPS + 2 EBM
40 / 60 / 105 / 287 55 / 82 / 143 / 396 49 / 74 / 133 / 358 24 / 36 / 64 / 172 33 / 50 / 87 / 237 23 / 35 / 64 / 172
UPS + 3 EBM
68 / 101 / 176 / 492 92 / 137 / 238 / 678 88 / 133 / 237 / 640 39 / 58 / 101 / 279 53 / 79 / 137 / 384 42 / 64 / 114 / 308
UPS + 4 EBM
99 / 146 / 255 / 729
134 / 199 / 346 / 1004
133 / 200 / 358 / 966
55 / 82 / 143 / 400 75 / 111 / 194 / 550 64 / 96 / 172 / 465
Given runtimes are estimates and valid at 20 degrees Celsius.
Actual runtime of the system will depend, among many variables, on the age of the batteries and
environmental conditions.