Program features 17
Country settings
Preset country codes
The PRO-33.0-TL inverter has a country code table with preset grid code settings for 37
countries. The installation country is initially set with the First start assistant or with the
parameter 188.01 Country code.
The First start assistant activates automatically when the inverter is turned on for the very
first time. See more details in the PRO-33.0-TL Product manual. The country code may
also have separate options for low voltage and medium voltage settings when there are
separate requirements for MV connection in the same country, such as Germany LV and
Germany MV. If the country code is not set, the inverter does not operate.
When a country code is selected, all the necessary parameter settings are set to match
the country requirements. The country code settings affects the parameters in the groups
124 Q ref, 130 Limits, 178 MPPT settings, 188 Grid monitoring, 189 Inverter control and
209 Misc. The parameters include, for example, nominal output values, tripping limits for
under- and overvoltage and under- and overfrequency, initial connection delays, variety of
reconnection delays, anti-islanding settings, reactive power settings, fault ride-through
settings, power limitation settings and MPPT recovery settings. Usually the country code is
not changed during the lifetime of the inverter.
You can change the country code with parameter 188.01 Country code.
Note: Changing this value will always override any changes made in the above-mentioned
parameter groups.
When a country code is initially set, all the preset parameters can be modified if they
adhere to the local grid code requirements. See details in chapter Customizing country
code settings on page 17.
Settings
188.01 Country code
Diagnostics
172.01 Connection status
Customizing country code settings
If the country code-related parameter settings (parameters in groups 124 Q ref, 130
Limits, 178 MPPT settings, 188 Grid monitoring, 189 Inverter control and 209 Misc) need
to be changed, follow this procedure:
Disable the inverter
1. Enter the Service menu.
2. Select Inverter operation and press Edit.
3. Change the value from Enable to Disable and press Save. After a short period, the
inverter stops running and it is possible to change the parameter values.
Customize settings
1. Enter the parameter list: Service menu - Parameters - Complete list.
2. Check that you have a country code set with parameter 188.01 Country code.
3. Make required changes to the parameters.