Parameters 57
No. Name/Value/Range Description Default
FbEq (16b/32b)
132 Autoreset
132.01 Autoreset counter Shows the number of autoresets. Can be cleared
to allow better monitoring.
0
- 1 = 1
132.02 Autoreset boot counter Counts the number of forced reboots. Some faults
can be reset / cleared only with a firmware reboot.
The counter increments when the Autoreset
function orders a reboot.
0
- - / 1 = 1
132.03 Overcurrent trials Sets the number of overcurrent autoreset trials. 5
0 … 20 1 = 1
132.04 Overcurrent reset delay Sets the delay for overcurrent autoreset. 10 s
1 … 3000 s 1 = 1 s
132.05 DC protection trials Number of DC protection autoreset trials. 3
0 … 20 1 = 1
132.06 DC protection reset delay Sets the delay for DC protection autoreset. 10 s
1 … 3000 s 1 = 1 s
132.07 Ground impedance trials Sets the number of ground impedance autoreset
trials.
50
0 … 100 1 = 1
132.08 Ground impedance reset
delay
Sets the delay for ground impedance autoreset. 900 s
1 … 7200 s 1 = 1 s
132.09 Ground current trials Sets the number of ground current autoreset
trials.
-
0 … 100 1 = 1
132.10 Ground current reset delay Sets the delay for ground current autoreset. -
1 … 7200 s 1 = 1 s