56 Parameters
130.81 P(U) release ramp Sets the ramp up after power limit release. 20%/min
0 … 100%/min 1 = 1%/min
130.90 Flat-top limit Sets the active power limit which cuts the semi-
circular operating range to a flat-top range.
200%
0 … 200% 1 = 1%
130.92 Active power ramping Enables the active power ramping function. Disable
Disable 0
Enable 1
130.93 Active power ramp Sets the active power ramp rate. 100%/min
0 … 1000%/min 1 = 1%/min
130.94 Shut down ramp Sets the active power ramp that is applied in a
controlled shut down.
100%/s
0 … 1000%/s 1 = 1%/s
130.98 External limit ramp up Sets the ramp up time for 130.75 External power
limit.
0 ms
0 … 60 000 ms 1 = 1 ms
130.99 External limit ramp down Sets the ramp down time for 130.75 External
power limit.
0 ms
0 … 60 000 ms 1 = 1 ms