Parameters 99
No. Name/Value/Range Description Default
FbEq (16b/32b)
209 Misc
209.06 Minimum ground
impedance
Sets fault level for ground impedance. 0.20 MOhm
0 ... 10 MOhm Fault level. - / 100 = 1
MOhm
209.10 Ext-IO status word Shows the status of output power.
b0: Grid connected True when connected to the grid.
b1: Power level 20% True when the output power is over 20%.
b2: Power level 40% True when the output power is over 40%.
b3: Power level 70% True when the output power is over 70%.
b4...15: Reserved -
209.11 Limit priority Defines whether active or reactive current has
priority when current must be limited.
Active current
Active current Limits reactive current before active current. 1
Reactive current Limits active current before reactive current. 2