54 Parameters
No. Name/Value/Range Description Default
FbEq (16b/32b)
130 Limits
130.01 Limit word 1 Shows active power limitation status. -
b0...b1: Reserved Reserved
b2: P max Maximum power level
b3: P min Minimum power level
b4: Reserved Reserved
b5: Power gradient Power gradient
b6: Stop ramp Stop ramp
b7: P(f) P(f) limitation
b8: Grid fault Power is limited after grid fault.
b9: Connect Power is limited after connection to grid.
b10: External External limit is active, 130.75 External power
limit.
b11: FRT recovery Power is limited after FRT event.
b12: P(U) P(U) limitation
b13: Flat-top Flat-top
b14: Input current Input current
b15: Grid current Grid current is limiting active power.
130.02 Limit word 2 Shows reactive power limitation status. -
b0: Q ref max Reactive power reference is limited by 124.11
Ireact ref max %.
b1: Q ref min Reactive power reference is limited by 124.12
Ireact ref min %.
b2...b14: Reserved Reserved
b15: Current Grid current is limiting reactive power.
130.04 Limit word 4 Shows current based limitation status. -
b0...b1: Reserved Reserved
b2: I max Maximum current
b3: CB temperature Control board temperature
b4: Inverter temperature IGBT temperature
b5: Filter temperature Line filter temperature
b6: Nominal power Nominal apparent power
b7...b15: Reserved Reserved
130.62 P(f) limit type Selects the P(f) limiter type. Disabled
Disabled P(f) limiter is disabled. 0
Free running Limit moves both ways along the gradient. 1
Incremental Limit only decreases along the gradient until the
frequency drops below the corner point
2
130.63 P(f) corner frequency Sets the starting point for limitation. 50.2 Hz
40 … 70 Hz 100 = 1 Hz
130.64 P(f) limit gradient Sets the limit gradient. 40%/Hz
0 … 200%/Hz 10 = 1%/Hz
130.65 P(f) release frequency Sets the frequency where the power limit is
released and ramping the limit up starts.
50.2 Hz
40 … 70 Hz 100 = 1 Hz