Parameters 53
- 1 = 1 /
10 = 1
124.30 Q(x) curve Selects the input signal used in Q(x) regulation
curve.
-
Q(U) Input: Measured grid voltage
Output: Reactive power reference
0
Q(P) Input: Actual active power
Output: Reactive power reference
1
CosPhi(P) Input: Actual active power
Output: CosPhi
2
124.31 Lock-in level Defines the lock-in level to activate the Q(x)
regulation curve.
20%
0 … 200% 1 = 1%
124.32 Lock-out level Defines the lock-out level to deactivate the Q(x)
regulation curve.
5%
0 … 200% 1 = 1%
124.33 Q(x) input level 1 Defines the first input value for the Q(x) regulation
curve. When the selected input signal reaches
this value, reactive power reference is set to the
value defined by parameter 124.39 Q(x) output
level 1.
0%
- 1 = 1% /
100 = 1%
... ... ... ...
124.38 Q(x) input level 6 See parameter 124.33 Q(x) input level 1.
124.39 Q(x) output level 1 Defines the first reference output value for the
Q(x) regulation curve. When the selected input
signal reaches 124.33 Q(x) input level 1, the
reactive power reference is set to the value
defined by this parameter.
0
- 1 = 1 /
100 = 1
... ... ... ...
124.44 Q(x) output level 6 See parameter 124.39 Q(x) output level 1
124.45 Q(U) activation delay Defines the activation delay for Q(U) curve. 0 ms
0...30000 ms Time 1 = 1 ms
124.46 Q(U) activation level low Defines the lower activation level for Q(U) curve. 100%
0...200% Activation level 1 = 1%
124.47 Q(U) activation level high Defines the higher activation level for Q(U) curve. 100%
0...200% Activation level 1 = 1%
No. Name/Value/Range Description Default
FbEq (16b/32b)