Parameters 75
Min DC voltage MPPT has reached the minimum DC voltage
level. System delivers power at the rate
necessary to maintain DC input voltage within the
operating range.
200
At power System delivers power according to the selected
power reference.
300
Disconnected Inverter is disconnected. 800
Other If none of the other reasons is valid, this value is
shown.
0
Max DC Voltage MPPT has reached the maximum DC voltage
level. System delivers power at the rate
necessary to maintain DC input voltage within the
operating range.
220
Active power limited Inverter limits active power. See parameter
130.01 Limit word 1.
500
172.04 Connection 1 date Latest connection date. -
172.05 Connection 1 time Latest connection time. -
172.06 Connection 2 date 2nd latest connection date. -
172.07 Connection 2 time 2nd latest connection time. -
172.08 Connection 3 date 3rd latest connection date. -
172.09 Connection 3 time 3rd latest connection time. -
172.10 Connection 4 date 4th latest connection date. -
172.11 Connection 4 time 4th latest connection time. -
172.12 Connection 5 date 5th latest connection date. -
172.13 Connection 5 time 5th latest connection time. -
172.20 Grid monitoring SW1 Shows grid monitoring status word 1 (SW1).
0 = Inactive status
1 = Active status, triggered or enabled
-
b0: Grid stable Criteria for stable grid conditions are fulfilled.
b1: Parameters All grid monitoring parameters are initialized
successfully.
b2...b15: Reserved
172.21 Grid monitoring SW2 Shows the grid monitoring status word 2 (SW2).
0 = Inactive status
1 = Active status, triggered or enabled
-
b0: Connect
underfrequency
b1: Connect overfrequency
b2: Connect undervoltage
b3: Connect overvoltage
b4: Underfrequency 1
b5: Underfrequency 2
b6: Overfrequency 1
b7: Overfrequency 2
b8: Undervoltage 1
No. Name/Value/Range Description Default
FbEq (16b/32b)