Parameters 97
196.26 Time in ms within one
minute
Sets the number of milliseconds passed since last
minute.
See parameter 196.24 Full days since 1st Jan
1980.
0 ms
0 ... 59999 ms Number of milliseconds since last minute. 1 = 1 ms
196.29 Time source status Shows the status and priority of active time
source.
b1: Aux Time tick received Time tick from the second priority source is
received.
b2: Tick interval is too long Accuracy of inverter’s time is compromised due to
a long tick interval.
b3: DDCS controller Tick is received from DDCS controller.
b4: Master/Follower Tick is received from Master/Follower link.
b5: Reserved -
b6: D2D Tick is received from D2D link.
b7: FbusA Tick is received from fieldbus adapter FBA.
b8: FbusB Not in use.
b9: EFB Tick is received from embedded fieldbus.
b10: Ethernet Not in use.
b11: Panel link Tick is received from PVS-AP-L control unit or the
Drive composer tool.
b12: Ethernet tool link Tick is received via FENA-11/21 over ethernet
from Drive composer tool.
b13: Parameter setting Time and date are set with parameters.
b14: RTC Not in use.
b15: Drive On-Time Time and date originate from the system clock of
the operating system. The status indicates that
system time was not synchronized with an
external time source for some time and time
keeping might not be accurate.
196.30 System time - days Reads system date, days since 31.12.1979.
1 = 1.1.1980
0
0 … 65535 1 = 1
196.31 System time - seconds Reads system time, seconds since 00:00:00 0
0...86399 1 = 1
196.51 Clear fault and event
logger
Setting this parameter to one (1) clears the fault
and event loggers. Parameter value returns to
zero automatically.
-
0 … 65535 1 = 1
No. Name/Value/Range Description Default
FbEq (16b/32b)