FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  83 
 
Menu / parameter  Description 
Device Setup / ...Sensor 
Qv Max DN  The value provides the lower volume flow at a flow velocity of 10 m/s. 
The value is set automatically via the selected nominal diameter. 
Qv Max 1  Setting the upper range value 1 (Measuring range = 0 to Qv Max 1) for the volume flow for forward flow and reverse flow . 
Default setting: 1 × Q
max
DN 
Qv Max 2  Setting the upper range value 2 (Measuring range = 0 to Qv Max 2) for the volume flow for forward flow and reverse flow .   
This parameter is only available if the value ‘Max2 active’ has been selected for the parameter ‘Qv Range Mode’. 
Default setting: 1 × Q
max
DN 
Qv Range Mode  Manual switchover between the measuring ranges (Max1 active / Max2 active) for the volume flow measurement. This 
parameter is only available if the value Qm and Qv or Range Mode Confighas been selected for the parameter ‘Qv only’ 
Sensor Location Tag  Entry of the measuring point tag for the sensor. 
Alphanumeric, max. 20 characters 
Sensor Tag  Enter the tag number of the sensor. 
Alphanumeric, max. 20 characters. 
...Operating Mode  Selection of submenu ‘...Operating Mode’ using  . 
 
Device Setup / ...Sensor / ...Operating Mode 
Flow Direction  Set the measuring direction for the sensor. 
As delivered, the device measures and counts in both flow directions. 
•  Forward & Reverse: The device measures in both flow directions. 
•  Forward only: The device measures only forward flow direction. 
•  Reverse only: The device measures only reverse flow direction. 
Default setting: Forward & Reverse 
Flow Indication  Inversion of the displayed flow direction. 
Default setting: Normal