84 FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
… 8 Operation
… Parameter descriptions
Menu / parameter Description
Device Setup / ...Transmitter
...Units Selection of submenu ‘...Units’ using .
Damping Select the damping.
The value set here (0.02 to 60 s) refers to 1 τ (Tau). The value refers to the response time for a step flowrate change. It
affects the instantaneous value in the display and at the current output.
Default setting: 1 second
Damping On/Off Switches the damping on or off.
Density Fixed Value If the flow count and display are performed using mass flow units, a fixed density value must be included in the
calculations. To convert to mass flow, a density value in the range of 0.01 to 5.0 g/cm
3
can be set.
...Cut Off Selection of submenu ‘...Cut Off’ using .
TX Location TAG Entry of the measuring point tag for the transmitter.
Alphanumeric, max. 20 characters
TX TAG Enter the tag number for the transmitter.
Alphanumeric, max. 20 characters
Plant Data Sync. Tx -> Sens
The settings are redundantly saved in two data modules. One of them is the SensorMemory, the other is the transmitter
motherboard (backplane).
By selecting ‘Tx -> Sens’, location-specific settings such as measuring range or damping are replicated from the
transmitter motherboard (backplane) to the SensorMemory.
Sens -> Tx
By selecting ‘Sens -> Tx’, location-specific settings such as measuring range or damping are replicated from the
SensorMemory to the transmitter motherboard (backplane).
Device Reset For service purposes only. Restart the device without having to switch the power supply on and off.
Restore Factory Def. All user-accessible parameters will be reset to the factory default settings.
...Feature Settings Selection of submenu ‘...Feature Settings’ using .
...System Zero Selection of submenu ‘...System Zero’ using .
Noise Reduction Activates the filter technology for noise reduction.
Filter: Off, Filter 15, 30, 60 (15: lower filtering, 60: strong filtering)
Filter setting affects 20 mA signal (damping).
Default setting: Off
...Piston Pump Enables improved measurement performance, especially in piston pump applications.
Filter On/Off: On/Off
Filter length: 3 to 30 sec
Strokes per minute: Indicates the piston pump strokes per minute