125
Operation of
output
contact
Channel State of
output (R, W,
P)
Recorded
functions (R)
Value
Output SO4 0,2 O48 O108 0/1
d)
Output SO5 0,2 O49 O109 0/1
d)
Enabling
activation of
output
contacts PO1,
PO2, PO3,
SO1, SO2,
SO3, SO4 and
SO5 via the
SPA bus
0,2 O51 - 0/1
a)
State of output when the trip lockout function is not in use.
b)
Either O43/O103 or O46 is to be used at a time.
c)
State of output when the trip lockout function is in use.
Parameters O41...O49 and O51 control the physical output contacts
which can be connected to circuit breakers, for instance.
Parameters for IEC 60870-5-103 remote communication protocol
Table 5.1.17.-12 Settings
Description Parameter
(channel 507)
R, W, P Value
Unit address of the relay 507V200 R, W 1...254
Data transfer rate (IEC 60870-5-
103), kbps
507V201 R, W (P) 9.6/4.8
Parameters for Modbus remote communication protocol
Table 5.1.17.-13 Settings
Description Parameter
(channel 504)
R, W, P Value
User-defined register 1 504V1 R, W 0...65535
a)
User-defined register 2 504V2 R, W 0...65535
a)
User-defined register 3 504V3 R, W 0...65535
a)
User-defined register 4 504V4 R, W 0...65535
a)
User-defined register 5 504V5 R, W 0...65535
a)
User-defined register 6 504V6 R, W 0...65535
a)
User-defined register 7 504V7 R, W 0...65535
a)
User-defined register 8 504V8 R, W 0...65535
a)
User-defined register 9 504V9 R, W 0...65535
a)
User-defined register 10 504V10 R, W 0...65535
a)
User-defined register 11 504V11 R, W 0...65535
a)
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310