127
Description SPA
parameter
(channel 503)
R, W Value range Default Explanation
Default variation of counter
objects
503V13 R, W 1...2 2
Default variation of counter
change event objects
503V14 R, W 1, 2, 5, 6 2
Default variation of frozen
counter objects
503V30 R, W 1, 2, 5, 6 2
Class 1 event delay 503V18 R, W 0...255 s 0
Class 1 event count 503V19 R, W 0...255 1
Class 2 event delay 503V20 R, W 0...255 s 0
Class 2 event count 503V21 R, W 0...255 1
Class 3 event delay 503V22 R, W 0...255 s 0
Class 3 event count 503V23 R, W 0...255 1
Unsolicited reporting mode 503V24 R, W 0 = UR disabled
1 = immediate
2 = empty UR
3 = empty UR and
enable UR
0 Refer to Unsolicited reporting start up in
Section 5.1.16.4. Specific DNP features.
Scaling factor 1 503V101 R, W 0...4294967295 1
Scaling factor 2 503V102 R, W 0...4294967295 1
Scaling factor 3 503V103 R, W 0...4294967295 1
Scaling factor 4 503V104 R, W 0...4294967295 1
Scaling factor 5 503V105 R, W 0...4294967295 1
Baud rate 503V211 R, W 4.8/9.6/19.2/38.4 9.6
Number of stop bits 503V212 R, W 1...2 1
Parity 503V230 R, W 0 = no parity
1 = odd
2 = even
0
Silent interval 503V232 R, W 0...65535 ms 20
Time slot width 503V233 R, W 0...255 ms 10
Number of time slots 503V234 R, W 0...255 8
Collision detection enabled 503V235 R, W 0 = disabled
1 = enabled
0
DNP module warning
register
503V168 R Bit coded
0=OK
DNP module status
register
503V169 R Bit coded
0=OK
Feeder Protection Relay