Table 5.1.15.1.-10 Mapping of Modbus data: relay identification
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Type designation of the relay 701...708 ASCII chars, 2
chars/register
Table 5.1.15.1.-11 Mapping of Modbus data: real-time clock
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Time reading and setting 721...727 W See Structure 4
Table 5.1.15.1.-12 Mapping of Modbus data: additional analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Thermal level 801 0...106 %
One-minute demand value 802 0...5000 0...50 x I
n
Demand value during the specified
time range
803 0...5000 0...50 x I
n
Maximum one-minute demand value
during the specified time range
804 0...5000 0...50 x I
n
Stage/phase which caused the trip 805 HI word 0...131071 See Table 5.1.17.-
3
806 LO word
Trip indication code 807 0...21 See Table 5.1.17.-
3
Number of starts of stage I> 808 0...999 Counter
Number of starts of stage I>> 809 0...999 Counter
Number of starts of stage I>>> 810 0...999 Counter
Number of starts of stage I
0
> 811 0...999 Counter
Number of starts of stage I
0
>> 812 0...999 Counter
Number of starts of stage ΔI> 813 0...999 Counter
Number of trips of stage I> 814 0...65535 Counter
Number of trips of stage I>> 815 0...65535 Counter
Number of trips of stage I>>> 816 0...65535 Counter
Number of trips of other stages 817 0...65535 Counter
Number of AR shots (shot 1) initiated
by the trip signal from stage I>>
818 0...255 Counter
Number of AR shots (shot 1) initiated
by the digital input signal
819 0...255 Counter
Number of AR shots (shot 1) initiated
by the start or trip signal from stage I>
820 0...255 Counter
Number of AR shots (shot 1) initiated
by the start or trip signal from stage I
0
>
821 0...255 Counter
Number of AR shots (shot 2) initiated
by the trip signal from stage I>>
822 0...255 Counter
Number of AR shots (shot 2) initiated
by the digital input signal
823 0...255 Counter
Number of AR shots (shot 2) initiated
by the start or trip signal from stage I>
824 0...255 Counter
96
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual