ABB RELION REX640 - Measurements and phasor diagrams; Viewing measurements; Viewing phasor diagrams

ABB RELION REX640
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remote Update. If the IED is in local control mode, remote update proceeds only
after a confirmation is received from the user.
Remote update can be disabled manually after the update.
Remote update only works when the IED is connected from the Ethernet interface
connector of the communication module with a custom IP address.
3.6.2 Updating firmware or language
1. Select the update mode.
Firmware
Language
2. Select the update package and click Next.
GUID-21873086-DFE3-4B23-872C-B954019B5EEC V1 EN
Figure 12: Choosing the update mode and package
3. Select the relay to be updated and click Next.
Currently only one relay can be selected.
1MRS759117 A Section 3
PCM600
REX640 35
Engineering Manual