3.17.7.1 Function block
Figure 92: Function block
3.17.7.2 Functionality
The set-reset (8 pcs) function SRGAPC is a simple SR flip-flop with a memory that
can be set or that can reset an output from the S# or R# inputs, respectively.
The function contains eight independent set-reset flip-flop latches where the SET
input has the higher priority over the RESET input. The status of each Q# output
is retained in the nonvolatile memory. The individual reset for each Q# output is
available on the LHMI or through tool via communication.
Table 170: Truth table for SRGAPC
S# R# Q#
0 0 0
1
0 1 0
1 0 1
1 1 1
3.17.7.3 Signals
Table 171: SRGAPC Input signals
Name Type Default Description
S1 BOOLEAN 0=False Set Q1 output when
set
R1 BOOLEAN 0=False Resets Q1 output
when set
Table continues on the next page