4.1.1.9 Settings
Table 234: FPHLPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.05...5.00 xIn 0.01 0.05 Start value
Start value Mult 0.8...10.0 0.1 1 Multiplier for scaling the
start value
Time multiplier 0.05...15.00 0.01 1 Time multiplier in IEC/ANSI
IDMT curves
Operate delay time 40...200000 ms 10 40 Operate delay time
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
-2=Recloser 2
-3=Recloser 3
-4=Recloser 4
-5=Recloser 5
-6=Recloser 6
-7=Recloser 7
-8=Recloser 8
-9=Recloser 8+
-10=Recloser 8*
-11=Recloser 9
-12=Recloser 11
-13=Recloser 13
-14=Recloser 14
-15=Recloser 15
-16=Recloser 16
-17=Recloser 17
-18=Recloser 18
-19=Recloser A
-20=Recloser B
15=IEC Def. Time Selection of time delay
curve type
Table continues on the next page
Protection functions 1MRS758755 C
228 REC615 & RER615
Technical Manual