Table 246: PHIPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Table 247: PHIPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.1.1.10 Monitored data
Table 248: FPHLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
FPHLPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 249: PHLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
PHLPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
233