Parameter Values (Range) Unit Step Default Description
Curve parameter D 0.46...30.00 1 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 321: EFLPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
Table 322: EFHPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.10...40.00 xIn 0.01 0.10 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...200000 ms 10 40 Operate delay time
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
15=IEC Def. Time Selection of time
delay curve type
Table 323: EFHPTOC Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
289