EasyManua.ls Logo

ABB RER615 - Page 359

ABB RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 175: Combined overadmittance and overconductance characteristic.
Left figure: classical origin-centered admittance circle combined with two
overconductance boundary lines. Right figure: admittance circle is set off from the
origin.
Combined overconductance and oversusceptance characteristic
The combined overconductance and oversusceptance criterion is enabled with the
Operation mode
setting set to "Go, Bo".
By setting
Directional mode
to "Forward", the characteristic is a combination of two
boundary lines with the settings
Conductance forward
and
Susceptance forward
.
See
Figure 176
.
By setting
Directional mode
to "Non-directional", the characteristic is a combination
of four boundary lines with the settings
Conductance forward
,
Conductance
reverse
,
Susceptance forward
and
Susceptance reverse
. See
Figure 177
.
For the sake of application flexibility, the boundary lines can be tilted by the
angle defined with the
Conductance tilt Ang
and
Susceptance tilt Ang
settings. By
default, the tilt angles are zero degrees, that is, the boundary lines are straight
lines in the admittance plane. A positive
Conductance tilt Ang
value rotates
the overconductance boundary line counterclockwise from the vertical axis. A
positive
Susceptance tilt Ang
value rotates the oversusceptance boundary line
counterclockwise from the horizontal axis.
In case of the non-directional conductance and susceptance criteria, the
Conductance reverse
setting must be set to a smaller value than
Conductance
forward
and the
Susceptance reverse
setting must be set to a smaller value than
Susceptance forward
.
Operation is achieved when the measured admittance moves outside the
characteristic.
The combined overconductance and oversusceptance criterion is applicable in
high-resistance earthed, unearthed and compensated networks or in the systems
where the system earthing may temporarily change during normal operation from
compensated to unearthed system.
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
359

Table of Contents

Other manuals for ABB RER615

Related product manuals