EasyManua.ls Logo

ABB RER615 - Page 425

ABB RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
It is essential to provide power frequency overvoltage protection, in the form of
time delayed element, either IDMT or DT to prevent equipment damage.
4.4.1.7 Signals
Table 431: PHPTOV Input signals
Name Type Default Description
U_A_AB SIGNAL 0 Phase to earth volt-
age A or phase to
phase voltage AB
U_B_BC SIGNAL 0 Phase to earth volt-
age B or phase to
phase voltage BC
U_C_CA SIGNAL 0 Phase to earth volt-
age C or phase to
phase voltage CA
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 432: PHPTOV Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.4.1.8 Settings
PHPTOV Group settings
Table 433: PHPTOV Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...1.60 xUn 0.01 1.10 Start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...300000 ms 10 40 Operate delay time
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
15=IEC Def. Time Selection of time
delay curve type
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
425

Table of Contents

Other manuals for ABB RER615

Related product manuals