EasyManua.ls Logo

ABB RER615 - Page 507

ABB RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
faults. As data sheet impedance per unit values are generally valid only for
a certain tower configuration, the values should be adjusted according to the
actual installation configuration. This minimizes the fault location errors caused by
inaccurate settings.
The positive-sequence reactance per unit and per phase can be calculated with a
following approximation equation which applies to symmetrically transposed three-
phase aluminium overhead lines without ground wires.
X
a
r
km
n
en
1
4
10 2 0 5 +
ω
ln . [ / ]
(Equation 59)
ω
n
2 × π × f
n
, where f
n
= fundamental frequency [Hz]
a
en
a a a
12 23 31
3
( )
the geometric average of phase distances [m]
a
xy
distance [m] between phases x and y
r radius [m] for single conductor
Figure 254: Typical distribution line tower configurations
Example values of positive-sequence impedances for typical medium voltage
overhead-lines are given in the following tables.
Table 534: Positive-sequence impedance values for typical 11 kV conductors, “Flat”
tower configuration assumed
Name R1 [Ω/km] X1 [Ω/km]
ACSR 50 SQ.mm 0.532 0.373
ACSR 500 SQ.mm 0.0725 0.270
1MRS758755 C Protection related functions
REC615 & RER615
Technical Manual
507

Table of Contents

Other manuals for ABB RER615

Related product manuals