Parameter Values
(Range)
Unit Step Default Description
29=U12
30=U23
31=U31
32=UL1
33=UL2
34=UL3
35=U12B
36=U23B
37=U31B
38=UL1B
39=UL2B
40=UL3B
Channel id
text
0 to 64 char-
acters, alpha-
numeric
DR analog
channel X
Identification
text for the
analog chan-
nel used in
the COM-
TRADE format
High trigger
level
0.00...60.00 pu 0.01 10.00 High trigger
level for the
analog chan-
nel
Low trigger
level
0.00...2.00 pu 0.01 0.00 Low trigger
level for the
analog chan-
nel
Storage mode
0=Waveform
1=Trend / cy-
cle
1 0 Storage mode
for the analog
channel
Table 643: RDRE Non-group binary channel settings
Parameter Values
(Range)
Unit Step Default Description
Operation
1=on
5=off
1 5=off Binary chan-
nel is enabled
or disabled
Level trigger
mode
1=Positive or
Rising
2=Negative or
Falling
1 1=Rising Level trigger
mode for the
binary chan-
nel
Table continues on the next page
Measurement functions 1MRS758755 C
624 REC615 & RER615
Technical Manual