Quick start-up guide
21
In case this happens, try to set the IP address again and make
sure that you typed everything correctly
Another way to set IP address is to use the control panel of the
drive. Set IP address to RETA-01 configuration parameters
51.04 - 51.07, subnet mask to parameters 51.08 - 51.11 and
gateway address to parameters 51.12 - 51.15 if necessary. Set
RETA-01 configuration parameter 51.27 to REFRESH to enable
the network settings.
Communication
The module is now ready to operate with Modbus/TCP or
EtherNet/IP protocol. The protocol and communication profile
used in the application can be selected with a RETA-01
configuration parameter, “PROTOCOL”:
Note: With ACS550 the profile selection is automatic. With
ACS800 the profile must be selected with parameter 98.07 as
follows:
Modbus/TCP: 98.07 = ABB DRIVES
Ethernet/IP AC/DC communication profile: 98.07 = GENERIC
Ethernet/IP ABB Drives communication profile: 98.07 = ABB
DRIVES
Modbus/TCP master configuration
Modbus/TCP is based on data registers, which hold IO and
parameter values. See chapter communication for register
mapping and supported function codes.
0 = Modbus/TCP
1 = EtherNet/IP AC/DC communication profile
2 = EtherNet/IP ABB Drives communication profile