EasyManua.ls Logo

ABB RETA-01 - Fault Tracing; LED Indications

ABB RETA-01
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault tracing
81
Fault tracing
LED indications
The RETA-01 module is equipped with three diagnostic LEDs. The
description of the LEDs is below.
Name Colour Function
Link/Activity
Green
Flashing green - Module is receiving/transmitting
on Ethernet
Steady green - Module has detected link
Off - Module cannot detect link
Network Status
Red/
Green
Flashing red - EtherNet/IP: One or more
connections timed out; Modbus/TCP: No message
has been received within configured time
Steady red - Duplicate IP address
Flashing green - Waiting for connections
Steady green - EtherNet/IP: At least one
EtherNet/IP connection is open against the
module (even to the Message router); Modbus/
TCP: At least one Modbus/TCP connection is
open against the module
Module Status
Red/
Green
Flashing red - Minor fault (e.g. communication
with application lost but recoverable)
Steady red - Major fault (e.g. bad flash, failed
memory test, non-recoverable communication
problem with host)
Steady green - Normal operation
Network Status
(not used) Link/Activity
Module Status

Table of Contents

Related product manuals