Drive configuration
38
When Ethernet/IP protocol is in use, these parameters define the
data words or drive parameters that can be sent using Assembly
object instance 102 (see chapter Communication).
The contents are defined by a decimal number in the range of
0 to 65535 as follows:
23 Input 1
24 Input 2
25 Input 3
26 Input 4
When Modbus/TCP protocol is in use, these parameters define
the input data words or drive parameters that are updated
cyclically between the drive and RETA-01. For the user this can be
seen as faster response for the Modbus queries.
When Ethernet/IP protocol is in use, these parameters define the
data words or drive parameters that can be read using Assembly
object instance 103 (see chapter Communication).
0 Not used
1…99 Data set area of the drive
1
Data set 1 word 1
2
Data set 1 word 2
3
Data set 1 word 3
4
Data set 2 word 1
5
Data set 2 word 2
• • • • • •
99
Data set 33 word 3
101…9999 Parameter area of the drive
Format: (x)xyy, where (x)x = actual
signal group or parameter group; yy
= actual signal or parameter index.
E.g. 103 = actual signal 01.03; 2202
= parameter 22.02.
10000…65535 Not supported by the drive