Assembly instances 20, 70, 21 and 71 are used in the AC/DC
drive profile and instances 100, 101, 102 and 103 in ABB Drives
profile. User selects the profile with RETA-01 configuration
parameter 16 PROTOCOL (with ACS800 also parameter 98.07 is
changed). The following table shows the possible combinations.
Note: Assembly instance 103 can be used with AC/DC drive
profile if it contains only drive parameters and not data sets.
The following table shows the possible combinations of output and
input instances.
RETA-01 configuration
parameter 16
Output instances Input instances
0 = Modbus/TCP - -
1 = Ethernet/IP AC/DC
communication profile
20, 21 70, 71, 103*
2 = Ethernet/IP ABB Drives
communication profile
100, 102 101, 103
Possible instance combinations
Output
instance
Input instance Communication profile to be
used
20 70 Generic Drive profile
71 Generic Drive profile
103 Generic Drive profile (See note
above)
21 70 Generic Drive profile
71 Generic Drive profile
103 Generic Drive profile (See note
above)
100 101 ABB Drives profile
103 ABB Drives profile
102 101 ABB Drives profile
103 ABB Drives profile