EasyManua.ls Logo

ABB RETA-02 - Diagnostics; RETA-02 LED Indications

ABB RETA-02
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
103
Diagnostics
LED indications
The RETA-02 module is equipped with three diagnostic LEDs. The
description of the LEDs in Modbus/TCP is presented below.
Name Colour Function
Link/Activity
Green
Off - Module cannot detect a link
Flashing green - Module is receiving/transmitting
on Ethernet
Steady green - Module has detected a link
Network Status
Red/
Green
Off - No power or IP address
Flashing green - Waiting for connections
Steady green - At least one Modbus/TCP
connection is open against the module
Flashing red - Connection timed out. No message
has been received within configured time
Steady red - Duplicate IP address
Module Status
Red/
Green
Steady green - Normal operation
Flashing red - Minor fault (e.g. communication
with application lost but recoverable)
Steady red - Major fault (e.g. bad flash, failed
memory test, non-recoverable communication
problem with host)
Network Status
(not used) Link/Activity
Module Status

Table of Contents

Related product manuals