Communication
71
Table 9.Parameter mapping
Register addresses, which are not allocated to any drive
parameter or data set, are invalid. Attempting to read from or write
to such an address will make the Modbus/TCP interface return an
exception code to the controller.
Refer to the drive manuals for drive-specific information such as
the data sets supported, and parameter numbers. Data set
registers are updated in a cyclic interval. Updating of parameter
registers happens at a slower interval.
Parameter 4GGPP GG PP
Data sets
Each data set consists
of 3 data words. For
example, ‘Data word
2.3’ refers to the 3rd
word in data set 2.
40001…40096 00 Data sets 01 Data word 1.1
02 Data word 1.2
03 Data word 1.3
04 Data word 2.1
05 Data word 2.2
06 Data word 2.3
07 Data word 3.1
94 Data word 32.1
95 Data word 32.2
96 Data word 32.3
Parameters 40101…40199 01 Group 01 01 Index 01
02 Index 02
99 Index 99
40201…40299 02 Group 02 01 Index 01
02 Index 02
99 Index 99
………
49901…49999 99 Group 99 01 Index 01
02 Index 02
99 Index 99