EasyManua.ls Logo

ABB SACE Emax E4.2 - Environmental Conditions

ABB SACE Emax E4.2
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Circuit-breakers E1.2-E2.2-E4.2-E6.2
3 - Environmental conditions
7 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
3 - Environmental conditions
Installation environment
Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that it is not subject
to shock or vibration.
If this is not possible, mount the circuit-breaker in a compartment protecting it adequately.
For the dimensions to be considered for installation, see the chapter "3 - Installation" on page 166 where
the references for following information can be found:
minimum installation volumes of the circuit-breakers and derived versions in a cell
overall dimensions of the circuit-breakers and the fixed parts
drilling of mounting holes
drilling of the cell door
Temperatures of the
installation environment
The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C, -13 °F e +158 °F.
Particular weather conditions
The circuit breaker is designed to operate in particularly difficult industrial environments.
It was tested according to:
IEC 60068-2-1: endurance at low temperatures
IEC 60068-2-2: hot dry climate
IEC 60068-2-30: hot humid climate
IEC 60068-2-52 severity 2: saline mist atmosphere
IEC 60947 (pollution level 3)
IEC60721-3-6 class 6C3
IEC60721-3-3 class 3C2
NOTE:
the circuit-breaker is suitable for installation in environments with saline concentrations
no higher than 10 mg/m3.
Dusty environments
It is recommended to install the circuit breaker in suitably ventilated switchgear where penetration by
dust is minimized.
In case of dusty environments (dust> 1 mg/m3) second level maintenance procedures must be followed.
Vibration
The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the following
standards:
IEC 60068-2-6
a) From 1 to 13 Hz with movement equal to 1 mm - 0.04 in b) From 13 to 100 Hz with
constant acceleration equal to 0.7 g - 0.025 lbs
Shipping Registers' specifications: RINA, BV, GL, ABS, LRs, DNV