ABB | SACE Emax 2
Ekip Touch - Protections
11 - Performance table
95 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
11 - Performance table
General notes:
• The performance values given in the next table are valid with ≥ 100 ms trip time, temperature
and signals within the operating limits; failure to comply with these limitations could lead to an
increase in the tolerances.
• Ekip Touch sends the TRIP command if the signal read exceeds the threshold for longer than the
set time (or the time resulting from the calculation formula)
• with an inverse time-delay trip curve, the calculation refers to a signal with a constant value
throughout the timing: variation of the alarm signal causes a different trip time
• The additional notes are given after all the tables
Standard Protections
Protection
[ANSI code]
Trip time t
t
(1)
Trip threshold
tolerance
(3)
Trip time tolerance
(3)
L [49]
(with curve t = k / I
2
)
Activation for If
within range: (1.05 to
1.2) x I1
with If ≤ 6 In: ± 10 % / with If > 6
In: ± 20 %
(with curves 60255-151)
S [50TD / 51]
t
t
= t2 ( with curve t =
k )
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between ± 10% and 40
ms
(with curve t = k / I
2
)
with If ≤ 6 In: ± 15 % / with If > 6
In: ± 20 %
S2 [50TD] t
t
= t5
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between ± 10% and 40
ms
I [50] t
t
≤ 30 ms ± 10 % --
G [50N TD /
51N]
t
t
= t4 ( with curve t =
k )
± 7 %
The best between ± 10% and 40
ms
(2)
(with curve t = k / I
2
)
± 15 %
MCR t
t
≤ 30 ms ± 10 % --
2I [50]
(10)
± 10 % --
IU [46] t
t
= t6 ± 10 %
with t6 ≥ 5 s: ± 100 ms / with t6 <
5 s the best between ± 10 % and
± 40 ms
Startup
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
S StartUp t
t
= t2 startup
with If ≤ 6 In: ± 7
% / with If > 6 In:
± 10 %
The best between ± 10% and 40
ms
I StartUp t
t
≤ 30 ms ± 10 % --
G StartUp t
t
= t4 startup ± 7 %
The best between ± 10% and 40
ms
S2 StartUp t
t
= t5 startup
with If ≤ 6 In: ± 7
% / with If > 6 In:
± 10 %
The best between ± 10% and 40
ms