ABB | SACE Emax 2
Ekip Touch - Protections
7 - ROCOF protections
81 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
7 - ROCOF protections
The ROCOF Protection package is available by default for Ekip G Hi-Touch and configurable in the
remaining models as additional SW package
The protection is described below:
ROCOF Protection
f28
t
t28
Hz/s
ROCOF
Function
ROCOF protection protects against rapid frequency variations: the protection sends a TRIP command if
the frequency changes faster than control variation f28 set in the unit for longer than t28.
f(Hz)
Frequency fluctuation
(after a failure)
Frequency variation
after failure
(1)
t28 t(s)
f28
f
mis
Figure 26
(1)
example with positive linear variation of the higher frequency of the set f28 value; the protection
also manages negative variations
The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 96)
the graph with trip curve (page 112)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold
f28
establishes the maximum admissible frequency variation rate over
time; the protection trips if this rate is exceeded.
The value is given as absolute value (Hz/s) Fn) and can be set within
the range: 0.4 Hz/s to 10 Hz/s in 0.2 Hz/s steps
0,6 Hz/s
Trip
Direction
Establishes whether the protection monitors an increase (Up), a
decrease (Down) or both variations (Up and Down)
Up or Down
Time f28
This is the trip time of the protection; the value is given in seconds
and can be set within a range: 0.06 s to 300 s, in 0.01 s steps
0,5 s
Limitations and additional functions