ABB | SACE Emax 2
Ekip Dip
7 - Default parameters
37 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
7 - Default parameters
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front
DIPs (protections, Frequency, Neutral), other via front bus.
Protection/Parameter Value
L 1 In; 144 s
S
(1)
Off; 0.1 s
I 4 In
G
(1)
Off; 0.1 s
Frequency 50 Hz (IEC) / 60 Hz (UL)
Neutral
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Hardware Trip Disabled
Local Bus Off
LED Alive Disabled (Power-on LED fixed)
Maintenance Off
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG
version.