ABB | SACE Emax 2
Ekip Touch - Protections
12 - Functions
98 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
12 - Functions
Introduction
This chapter includes the trip curves of the protections, which are shown in different point charts:
The curves are represented considering the maximum and minimum values of the parameters of
each protection, including the TRIP functions provided (current, time).
Protections with several curves (example: S protection), are shown in several graphs.
The curves do not take account of the effects of special parameters, such as thermal memory and
startups.
NOTE:
it is advisable to always use the mathematical function in the summary table of the
protections to calculate the trip time (page
95
)
This chapter illustrates the electronic trip curves of the available protections with all the protection trip
units for SACE Emax 2 circuit-breakers, represented in various dot diagrams. Some notes for reading the
diagrams:
The curves are illustrated considering the minimum and maximum values and of the parameters
of each protection.
The curves do not take account of the effects of special parameters such as thermal memory,
startup, etc.
Where version is not present, the curves are valid for both the IEC version and the UL version.
NOTE:
trip curve modeling software should be consulted when conducting a coordination
or arc flash study as these are simplified representations of the protection curves.
Function L (t = k/I
2
)