ABB | SACE Emax 2
Ekip Touch - Protections
11 - Performance table
97 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Additional protections
Protection
[ANSI code]
Trip time t
t
(1)
Trip threshold
tolerance
(3)
Trip time tolerance
Gext [50GTD /
51G]
t
t
= t41 ( with
curve t = k )
± 7 %
The best between ± 10% and 40 ms
(with curve t =
k / I
2
)
± 15 %
Rc [64 50N TD
87N]
t
t
= tdn -20 % ÷ 0
140 ms @ 0,06 s
(9)
950 ms @ 0,8 s
(9)
MDGF
t
t
= t41 ( with
curve t = k )
± 7 %
The best between ± 10% and 40 ms
(with curve t =
k / I
2
)
± 15 %
Startup
Protection
[ANSI code]
Trip time t
t
(1)
Trip threshold
tolerance
(3)
Trip time tolerance
Gext StartUp t
t
= t41 startup ± 7 % the best between: ± 10 % and ± 40 ms
MDGF StartUp t
t
= t41 startup ± 7 % the best between: ± 10 % and ± 40 ms
Note on protections
(1)
use trip and threshold current values expressed in In for calculating t
t
(example: If = 0.8 In, I1= 0.6
In)
(2)
with t4 = instantaneous, the maximum tolerance is 50 ms
(3)
Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time ≥
100 ms, temperature and signals within operating limits; the tolerances in the table after the notes
are applicable if the conditions are not guaranteed
(4)
the trip unit considers 3% hysteresis for quitting alarm condition
(5)
tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
frequencies
(6)
± 20% for threshold 0.4 Hz / s
(9)
maximum trip time
(10)
with If 18 kA, t
t
3 ms;
with If < 18 kA and If ≥ I31 * 3, t
t
7 ms (If three-phase) or t
t
9 ms (If single-phase);
with If < 18 kA and If < I31 * 3, t
t
15 ms.
(operating parameters guaranteed with Vaux auxiliary power supply)
(11)
tolerance valid with threshold U14 > 10%; with U14 ≤ 10% (and >6%), the tolerance is 10%; with
U14 < 5%, the tolerance is 15%
Performance guaranteed in all operating conditions
Protection Trip threshold tolerance Trip time tolerance
L
Activation within range: (1.05 to 1.2)
x I1
± 20 %
S ± 10 % ± 20 %
I / 2I ± 15 % ≤ 60 ms
G ± 15 % ± 20 % (60 ms with t4 = instantaneous)
Gext ± 15 % ± 20 %
MDGF ± 15 % ± 20 %
UF / UF2 /
OF / OF2
± 2 % ± 20 %
RV ± 10 %
± 20 %; in the case of single-phase self-
supply: the highest between ± 20 % and 30
ms
Other -- ± 20 %