EasyManua.ls Logo

ABB SACE Emax E4.2 - Page 99

ABB SACE Emax E4.2
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Ekip Touch - Protections
11 - Performance table
96 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Voltage protections
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
UV [27] / UV2 [27] t
t
= t8 (t15) ± 2 %
(4)
with t8 ≥ 5 s: ± 100 ms / with t8 < 5 s: the
best between ± 10 % and ± 40 ms
OV [59] / OV2 [59] t
t
= t9 (t16) ± 2 %
(4)
with t9 ≥ 5 s: ± 100 ms / with t9 < 5 s: the
best between ± 10 % and ± 40 ms
VU [47] t
t
= t14 ± 5 %
(11)
with t14 ≥ 5 s: ± 100 ms / with t14 < 5 s: the
best between ± 10 % and ± 40 ms
Voltage Advanced protections
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
S(V) [51V] / S2(V)
[51V]
t
t
= t20 (t21) ± 10 %
with t20 ≥ 5 s: ± 100 ms / with t20 < 5 s:
the best between ± 10 % and ± 40 ms
RV [59N] t
t
= t22 ± 10 %
with t22 ≥ 5 s: ± 100 ms / with t22 < 5 s: the
best between ± 10 % and ± 40 ms
Frequency protections
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
UF [81L] / UF2
[87L]
t
t
= t12 (t17) ± 1 %
(5)
with t12 ≤ 5 s: ± 100 ms / with t12 < 5 s:
the best between ± 10 % (min = 30 ms)
and ± 40 ms
OF [81H] / OF2
[87H]
t
t
= t13 (t18) ± 1 %
(5)
with t13 ≥ 5 s: ± 100 ms / with t13 < 5 s: the
best between ± 10 % and ± 40 ms
Power protections
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
UP [32LF] t
t
= t23 ± 10 %
with t23 ≥ 5 s: ± 100 ms / with t23 < 5 s:
the best between ± 10 % and ± 40 ms
OP [32OF] t
t
= t26 ± 10 %
with t26 ≥ 5 s: ± 100 ms / with t26 < 5 s:
the best between ± 10 % and ± 40 ms
RQ [40 o 32R] t
t
= t24 ± 10 %
with t24 ≥ 5 s: ± 100 ms / with t24 < 5 s:
the best between ± 10 % and ± 40 ms
OQ [32OF] t
t
= t27 ± 10 %
with t27 ≥ 5 s: ± 100 ms / with t27 < 5 s: the
best between ± 10 % and ± 40 ms
D [67] t
t
= t7
with If ≤ 6 In: ± 7
% / with If > 6 In:
± 10 %
with t7 ≥ 400 ms: ± 40 ms / with t7 < 400
ms: ± 20 ms and ± 10%, whichever is the
highest
RP [32R] t
t
= t11 ± 10 %
with t11 ≥ 5 s: ± 100 ms / with t11 < 5 s: the
best between ± 10 % and ± 40 ms
Startup
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
D StartUp t
t
= t7 startup ± 10 % The best between ± 10% and 40 ms
UP StartUp t
t
= t23 startup ± 10 %
with t23 ≥ 5 s: ± 100 ms / with t23 < 5 s:
the best between ± 10 % and ± 40 ms
ROCOF Protection
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
ROCOF [81R] t
t
= t28 ± 10 %
(6)
the best between ± 20% and 200 ms