8 - Protection Adaptive
82 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
8 - Protection Adaptive
The Adaptive Protection package is available by default for Ekip Hi-Touch and Ekip M Touch and
configurable in the remaining models as additional SW package.
The protection is described below:
Dual Set
The function enables two different protection configurations to be made, one as an alternative to the
other, by means of a set change with programmable events.
The function can be activated in the
Settings
-
Dual Set
menu (page 49)
Parameter Description Default
Enable
Activates/deactivates the function OFF
Default Set
Defines the sets of main and secondary protections (which
activate in the presence of the programmed event)
Set A
The event that determines set change (from default to secondary) can be programmed in the
Advanced
-
Functions
menu, see the paragraph Programmable Functions and Commands (page 92).