ABB | SACE Emax 2
Ekip Touch - Measurements
4 - Datalogger
122 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Parameters 2
The
Datalogger 1
and
Datalogger 2
submenus (available if the number of dataloggers selected is: 2)
contain the following options:
Parameter Description Default
Stop Event
Trigger event at which the recording is to be interrupted; the
main protection options (trips, timings, alarms) and the actuator
status (open/closed) are displayed.
The Custom option can be configured via Ekip Connect
None
Stop delay
Recording interruption delay, calculated from the trigger; the
value is given in seconds and can be set within a range: 0 s to 10
s, in 0.01 s steps
0.01 s
Restart Recording start command
Stop Manual recording stop command
Memory Type
Ekip Connect enables the
Memory Type
(Non volatile/Volatile) to be selected:
•
Non volatile
, Ekip Touch maintains the registration even when off; the life of the internal battery
of the unit can be sensibly less than the declared value in the absence of auxiliary power supply.
•
Volatile
: Ekip Touch loses the recording if it is switched off; when the unit is switched on again,
the datalogger automatically restarts, losing the previously stored data.
The parameter is configured by default as Non volatile.
Signallings
If there is a recording present, Ekip Touch provides the information on the diagnosis bar (DLog1 available).
NOTE:
In the configuration with two dataloggers, the specific indication of the available
recording is shown (DLog1 available or DLog2 available)
Ekip Connect
Ekip Connect 3 has two specific areas for the Datalogger function:
• Datalogger for configuring the recording parameters with a user-friendly interface, and for
downloading the recordings
• Data Viewer for opening and consulting the recordings
Both areas are available in the Tools menu of Ekip Connect.