ABB | SACE Emax 2
Ekip Touch - Measurements
5 - Network Analyzer
124 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Sags Menu
All the thresholds are given as a percentage of rated voltage Un and can be set from 10% to 95% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter Description Default
V sag Th Short Control threshold of
Sags Short
counter 10 % Un
V sag dur Short
Minimum duration of sag below the Short threshold to validate
the count of the
Sags Short
counter
0,8 s
V sag Th
Middle
Control threshold of
Sags Middle
counter 45 % Un
V sag dur
Middle
Minimum duration of sag below the
Middle
threshold to validate
the count of the
Sags Middle
counter
0,8 s
V sag Th Long Control threshold of
Sags Long
counter 95 % Un
V sag dur Long
Minimum duration of sag below the Long threshold to validate
the count of the
Sags Long
counter
0,8 s
NOTE:
Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle V sag dur Short
Swells Menu (Swell)
All the thresholds are given as a percentage of rated voltage Un and can be set from 105% to 125% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter Description Default
V swell Th
Short
Control threshold of the Swell
Short
counter 125 % Un
V swell dur
Short
Minimum duration of swell above the
Short
threshold to validate
the count of the
Swell Short
counter
0,8 s
V swell Th Long Control threshold of the
Swells Long
counter 105 % Un
V swell dur
Long
Minimum duration of swell above the Long threshold to validate
the count of the
Swells Long
counter
0,8 s
NOTE:
Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle V sag dur Short
Harmonics (Current and Voltage)
All the thresholds are given as a percentage and can be set within the range: 5% to 20% (total THD) or: 3%
to 10% (single harmonics) in 1% steps.
Menu Parameter Description Default
Current
THD
Threshold
Control threshold of the
THD Voltages
counter 5 %
Single
harmonic th
Control threshold of the single harmonics counters of
the voltages
5 %
Voltage
THD
Threshold
Control threshold of the
THD Current
counter 5 %
Single
harmonic th
Control threshold of the single harmonics counters of
the currents
5 %