ABB | SACE Emax 2
Ekip Touch - Test
1 - Test
137 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Ekip Signalling 4K
The menu activates in the presence of module
Ekip Signalling 2K
and auxiliary power supply.
The
Autotest
command is available in the menu; it activates the automatic output test sequence (contacts
and leds) and provides for the following operations:
Opening of the output contacts and switching off of output leds
Closing in sequence of the four output contacts and switching on of the relative leds
Reset initial conditions
IMPORTANT: the Autotest command closes the contacts regardless of the configuration
set by the user: the user is responsible for making the devices connected to the modules
secure, checking that the contacts have closed properly and that the leds have come on
Ekip Signalling 2K
The menu activates in the presence of module
Ekip Signalling 2K
, auxiliary power supply and local bus
enabled.
NOTE:
a menu is available for each Ekip Signalling 2K module present, up to a maximum of
three
The
Autotest
command is available in each submenu; it activates the automatic output test (Contacts and
leds), input test (leds) and provides for the following operations:
1. Resetting of output contacts (= open) and leds (= off).
2. Lighting up of all leds in sequence (output and input)
3. Closing and switch-off in sequence of the two output contacts while the relative leds come on.
4. Reset initial conditions
IMPORTANT: the Autotest command closes the contacts regardless of the configuration
set by the user: the user is responsible for making the devices connected to the Ekip
Signalling 2K modules secure, checking that the contacts have closed properly and that
the leds have come on
ZoneSelectivity
The menu has one or two sections, visibility of which depends on the protections available and enabled:
Submenus Reference selectivity Outputs/Inputs managed
S Selectivity S, S2, D (Forward) SZi (DFi), SZo (DFo)
G Selectivity G, Gext, MDGF, D (Backward) GZi (DBi), GZo (DBo)
Each submenu has three fields for checking selectivity inputs and outputs:
Field Description
Input Provides the status of the selectivity input (On/Off)
Force output Selectivity output activated
Force Output Selectivity output deactivated
Consult the description of the putting into service procedure when checking the selectivity contacts in
the manuals 1SDH000999r0002 and 1SDH001000r0002.
RC test
The command is available in the presence of
Rating plug Rc
and Rc toroid.
Selection of the command accesses a window containing the protection settings and test instructions:
1. Press the iTEST button to send a test signal to the toroid.
2. The toroid sends Ekip Touch a signal as though it had measured an alarm current.
3. Ekip Touch sends a TRIP command.
IMPORTANT: the command sends a signal to the Rc toroid and concludes with a TRIP
command: the user is responsible for checking that the initial connections are correct
(of the toroid and power supplies of the unit) and that TRIP is accomplished