ABB | SACE Emax 2
Mechanical characteristics
3 - Installation
169 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Positioning of anchor plates for Terminals FL
The anchor plates must be positioned as indicated in the figure.
150
mm
110
mm
Bus Bracing
Bus Bracing
Figure 107
>690V version IEC circuit-
breakers
>690V disconnectors and circuit-breakers are available in the following configurations:
Circuit-breaker Voltage Version
E1.2/E9 800 V F
(1)
- W
(2)
E2.2/E9/E10 800/900/1000 V F
(3)
- W
E4.2/E9/E10/E12 800/900/1000/1150/1200 V F
(3)
- W
E6.2/E9 800/900 V F
(3)
- W
(1)
Mandatory provision with front terminals (F) and high terminal covers (HTC)
(2)
Mandatory provision with positionable rear terminals (HR/VR) and phase separators (PB)
(3)
Insulating protections are mandatory for >690 V fixed versions of E2.2, E4.2 and E6.2.
Details about assembling insulating protections are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 1SDH001000r0746.
>635V version UL circuit-
breakers
>635V disconnectors and circuit-breakers are available in the following configurations:
Circuit-breaker Voltage Version
E4.2H-A/E 730V F
(1)
(1)
With insulating protections
Details about assembling insulating protections are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 1SDH001000r0746.