ABB | SACE Emax 2
Internal electronic accessories
3 - Ekip Signalling 4K
209 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Interface
The module has nine signaling leds:
Figure 125
LED Description
Power Signals the state of the module (on or off)
O 01, O 02, O 03, O 04
Indicate the physical state of the contacts of each output:
• off (contact open);
• on (contact closed).
I 01, I 02, I 03, I 04
Indicate the physical state of the contacts of each input:
• off (circuit open);
• on (short circuit).
Menu
The specific configuration area will activate in the
Settings
-
Modules
menu if the
Ekip Signalling 4K
module
is connected correctly to Ekip Touch.
The programming submenus of the inputs and outputs are present inside.
Output parameters
All the available outputs enable the following parameters to be configured:
Parameter Description Default
Signal source
Event which activates the output and changes the state of the contacts.
Different protection proposals, statuses and thresholds are available in
the menu; the Custom mode can be configured via Ekip Connect so as to
extend the solutions and combine several events.
None
Delay
Minimum presence of Source for output activation; the Delay is given in
seconds and can be set within a range between 0 s and 100 s, in 0.01 s
steps.
NOTES:
output will not activate if Source deactivates before Delay has
elapsed
if delay = 0 s Source must still be present for longer than 300 mS
0 s
Contact Type
Defines the rest status of the contact with Source not present between
either: normally open (NO) and closed (NC).
Output activation coincides with the change in state with respect to that
of rest.
NO
Latched
(1)
Allows the output to be managed differently when Source disappears:
either keep contact activated (On) or deactivate it (Off).
NOTE:
if Self-latching = On, the output resets if the module
switches off, or in the case of a module auto test or signal reset
command
Off