EasyManua.ls Logo

ABB SACE Emax E4.2 - Page 217

ABB SACE Emax E4.2
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
External electronic accessories
2 - Ekip Com Modbus RTU
214 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Interface
the module has three signaling leds:
Figure 126
LED Description
Power
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on and
communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent
Rx
Indicates the status of the communication between network master and module
(slave):
• off: Modbus RTU communication not activated
• on with fast flashes: Modbus RTU communication activated
Tx
Indicates the status of the communication between network master and module
(slave):
• off: communication between Modbus RTU not activated
• on with fast flashes: Modbus RTU communication activated
Configurations
ON
1 2 3 4
Figure 127
Resistor Dip Description Default
Rterm 1 and 2
120 Ω termination resistor
Move dip-switches 1 and 2 to the ON position to
connect Rterm
Off
Rpol 3 and 4
220 Ω pull-up or pull-down resistor
Move dip-switches 3 and 4 to the ON position to
connect Rpol
Off
IMPORTANT: move the dip-switches before connecting the module to Ekip Supply and
the communication network