ABB | SACE Emax 2
External electronic accessories
8 - Ekip Com IEC 61850
235 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred
configuration file
If several configuration files are present, allows file hierarchy
between .cid and .iid to be defined
.cid
Enable IEEE 1558
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
IEEE 1558 Master
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1558 Delay
mechanism
Allows the data exchange mode between module and master,
either Peer-to-Peer or End-to-End, to be selected.
End-to-
End
Time zone
Defines the time zone to be used for synchronism +00:00
Daylight Saving Time
Used to select whether daylight saving time is present (ON) or
not (OFF) in the country to which the synchronization time refers
OFF
TFTP Security level
Defines the file loading procedure:
TFTP always On
= port open, loading always possible
TFTP enable required
= port normally closed. To start loading,
Enable TFTP
must be run at the start of the procedure and
Disable TFTP
must be run at the end of the procedure (disable
not necessary, security command).
TFTP
always
On
CB Open/CB Close
command
Defines the limitations to remote opening and closing command
execution:
Standard commands
= standard commands (unrestricted)
activated
CB operate request
= standard commands not activated. Use
programmable functions YC COMMAND and YO COMMAND,
and Request breaker open (28) and Request breaker close (29)
commands
Standard
commands
Zone Selectivity
Analysis
Analysis of selectivity input from IEC 61850 module can be
enabled/disabled for each of protections S, S2, G, Gext, D, D(BW),
D(FW)
Disabled
(all)
IEEE 1588 Boundary
clock
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
clock by all the slaves/devices in the same local network, even
when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
OFF
Enable package
Limitation
Enables the Rate limiter function, which limits the number of
packages entering the module from the network, to be activated/
deactivated
Disable
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version
General module information
Flash CRC status and result
Information about the correctness of the SW in
the module
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server Synchronization
State of synchronism with SNTP server
IEEE 1558 status
Valid with Master IEEE 1588= ON, notifies the
presence (Slave or PTP Master Active) or absence
(PTP Master but Passive) of a higher level master
GOOSE Missing
Signals that an expected GOOSE has not been
received
Configure Mismatch
A GOOSE received does not conform to the
expected structure
Decode Error
Sequence number error
Remote programmable statuses (from E to R)
Condition (true/false) of the programmable states and
information on selectivity arising from logic defined in the
configuration files loaded in module IEC 61850
Zone selectivity remote inputs