ABB | SACE Emax 2
Ekip Touch - Interface and menus
1 - Presentation of interface
39 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
LED
LED Colour Description
Power
Green
Indicates the on status of Ekip Touch:
• off: no power and unit off
• on, steady (
Power mode
) or flashing (
Alive mode
): unit on and self-
supplied by external
Vaux
or service connector
The
Power mode
or
Alive mode
can be selected via Ekip Connect: if the
Alive mode
has been selected and external modules are connected, the
Power leds of Ekip Touch and the modules flash in the synchronized
mode.
Warnings
Yellow
Signals that certain alarms are present:
• off: no alarm
• on: steady prealarm of an active protection or status contacts error
• two flast flashes every 0.5 s: trip unit parameter configuration error
• fast flash:
Rating Plug
or
Measurement
module installation error
Alarm
Red
Signals that an alarm is present:
• off: no alarm
• on and steady: TRIP signalling due to protection or internal error; check
message on diagnosis bar to find out which
• fast flash: one or more of the following signals: protection timing
active, disconnection of a current sensor, trip coil disconnected, failed
trip command
• two flast flashes every 2 seconds:
Rating Plug
error
If on at the same time, the Warning and Alarm leds provide further signals:
LEDs on and flashing fast: absence of communication between Trip unit and Mainboard or T
protection timing
leds on with slow flashing: internal error
These cases need assistance from ABB.
Push-buttons
Push-
button
Description
HOME
Allows different areas of the menu to be accessed:
• from pages
HOME, Histograms, Measuring instruments, Measurements, Main
measurements
open the page
Main page
;
• from pages
Main page, Alarm list
, at any point of the menu area open:
HOME
page.
iTest
Allows certain pages of information about the unit to be rapidly consulted; press the
button in succession to display the following pages:
Alarm list
, if messages are present;
Info
, if Customer Page option is active;
Protection unit
, with information about Ekip Touch;
Circuit breaker
, with information about the CB;
Last trip
, with information about the last trip, if available.
Consultation is active from pages:
HOME, Histograms, Measuring instruments,
Measurements, Main measurements
NOTE:
with Ekip Touch off and the internal battery charged, press
iTEST
to
temporarily switch on the Power led and, in the case of a trip, the display with
information about the trip protection and the Alarm led
Service connector
The service connector enables Ekip Touch to be connected to
Ekip TT
,
Ekip T&P
and
Ekip Programming
,
allowing the unit to be temporarily supplied, parameter configuration prior to putting into service, tests
and extension of the configuration functions.
IMPORTANT: only use cables supplied by ABB or with ABB accessories