Ekip Touch - Protections
2 - Standard Protections
63 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
IU Protection
I6
t
t6
I
IU
Function
The protection trips if the current readings are unbalanced; the protection sends a TRIP command if the
detected unbalance exceeds threshold I6 for longer than t6.
The protection is automatically self-excluding in two cases:
the measurement of at least one current exceeds 6 In
the maximum current value between all the phases is less than 0.25 In (in I Avg configuration) or
0.3 In (in I Max configuration)
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 95)
the graph with trip curve (page 105)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Algorithm
Allows the unbalance calculation mode to be selected:
• With respect to I
max
: % Sbil = 100 x (I
max
- I
min
) / I
max
• With respect to: I
Avg
: % Sbil = 100 x (max I
Avg
) / I
Avg
NOTE:max I
Avg
: maximum deviation among the measured currents,
calculated by comparing each current with the mean value;
I
Avg
: mean value of the current readings
With
respect
to I
max
Threshold I6
Establishes the unbalance value that trips the protection.
Unbalance is given in percentage value within the range: 2% to 90% with
1% steps.
50 %
Time t6
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.5 s to 60 s, in 0.5 s steps
5 s
Neutral Protection
Function
Neutral protection characterizes protections L, S and I differently on the neutral phase by introducing a
different control factor from the other phases.
The protection is available with the 4P and 3P + N configuration; the configuration parameters can be
accessed via the Settings menu (page 49).
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection OFF
Neutral
threshold
Defines the multiplicative factor applied to the trip thresholds and
curves of the protections for the current read on phase Ne:
• 50 %: lowest trip thresholds for the neutral current
• 100 %: same trip thresholds for all phases
• 150 %: highest trip thresholds for the neutral current
• 200 %: highest trip thresholds for the neutral current
50 %
Limitations and additional functions
Ekip Touch rejects modification of thresholds I1 and InN in the absence of the following limitation: (I1 x
InN) ≤ Iu
I1 is the threshold of L protection in amperes (example: In= 400 A and I1= 0.6 becomes I1= 240 A)I1
is the threshold of L protection in amperes (example: In= 800 A and I1= 0.6 becomes I1= 480 A)
InN is the neutral threshold expressed as multiplicative factor (example: InN= 200% becomes InN= 2)
Iu is the size of the CB
WARNING! With 150% and 200% threshold; if the measured neutral current exceeds 16In,
the Trip unit resets the protection to 100% by itself