Ekip Touch - Protections
4 - Voltage Advanced protections
69 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Parameter Description Default
Threshold Ul
This is the voltage that determines the change in trip threshold
I20; the behavior differs, depending on the mode selected
(1)
The value is given as both absolute value (V) and relative value
(Un) and can be set within the range: 0.2 Un to 1 Un in 0.01 Un
steps
1 Un
Threshold Uh
The parameter is shown by the Lin curve and contributes towards
I20 trip threshold calculation:
with voltage reading < Uh (and ≥ Ul), the threshold changes
gradually
(1)
with voltage reading ≥ Uh, the threshold is I20
The value is given as both absolute value (V) and relative value
(Un) and can be set within the range: 0.2 Un to 1 Un in 0.01 Un
steps
1 Un
Threshold Ks
I20 threshold calculation constant.
The value is given as percentage of threshold I20 and can be set
within the range: 0.1 I20 to 1 I20, in 0.01 steps
0,6 I20
Time t20
This is the trip time of the protection.
The value is given in seconds and can be set within the range:
0.05 s to 30 s, in 0.01 s steps
0.1 s
(1) Trip threshold (depending on the operating curve)
Mode Voltage reading Trip threshold
Scal
< UI Ks x I20
≥ UI I20
Lin
< UI Ks x I20
≥ Ul (e < Uh) ((I20 x ( 1 - Ks ) x ( U
mis
- Uh ) ) / (Uh - Ul) ) + I20
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 86).
S(V) Protection
I21
t
t21
I
S2(V)
Function
S2(V) protection functions in the same way as S(V) protection and protects against short-circuits, with
threshold sensitive to the voltage value.
It is independent of S(V) protection, thus thresholds and functions of the two protections can be
programmed so as to take advantage of different plant solutions (example: signaling with S(V) and open
command with S2(V) or vice versa, or both S(V) and S2(V) for signaling or tripping).
If the current of one or more phases exceeds threshold I21 for longer than time t21, the protection activates
and sends a TRIP command.
Following a voltage drop, the I21 threshold varies according to two different modes:
Step provides for a stepped variation, depending on parameters Ul2 and Ks2.
Lin (linear) provides for a dynamic variation, depending on parameters Ul2, Uh2 and Ks2.
V
I21
Ks2 x I21
Uh2
Ul2
V
I21
I21 I21
Ks2 x I21
Ul2
Figure 24
To check and simulate the trip times in relation to all the parameters, please consult:
the summary table of the protections with the calculation formulas (page 96)
the graph with trip curve (page 107)
Continued on the next page