Field mountable paperless recorder 7 Configuration
68 IM/SM500F Rev. Z
Referring to Fig. 7.3, set the internal security switch as follows:
a Unlock the recorder's door with the key supplied, press the release catch and open the door.
b Remove the tamper-evident seal (if fitted), release the captive screw securing the inner cover plate
and remove the inner cover plate.
c Set the Security switch to the 'Configuration Level Not Protected' position (toward bottom of
recorder).
d Locate the inner cover plate lugs in the slots in the outer case and close the inner cover plate.
e Tighten the inner cover plate retaining screw and fit a tamper-evident seal (if required).
f Close and lock the recorder's door and restore the power supply to the recorder.
Warning. Before proceeding to step 2, isolate the recorder from the power supply.
Note. The Internal Security Switch is used to access the Configuration level when 'Configuration
security' is set to 'Switch protected'. Do Not use the switch to access the Configuration level
when 'Configuration security' is set to 'Password protected' (default setting) unless the Password
has been forgotten. The switch overrides Password protection, enabling free access to the
Configuration level.
Fig. 7.3 Setting the Security Switch
3
1
4
5
6
2
Configuration Level Protected
Configuration Level Not Protected